| Engineering Services: Automated Damage
Control System Development
DDG-51 CLASS CHILLED WATER AUTOMATION
SYSTEM (CWAS) LAND-BASED PERFORMANCE TEST (LBPT) FACILITY CONTROL AND
MONITORING SYSTEM (CMS)
A Chilled Water Automation System (CWAS)
is currently under development for deployment on DDG-107 and follow.
The system is to provide automated damage control for the ship’s chilled
water plant. It is to rely on programmable automated valves (PAVs) – or
smart valves – and flow sensors installed in the CW plant expansion tank
outlet piping to detect and isolate ruptures within the closed-loop
piping system.
To test the CW system being developed,
a Land-based Performance Test (LBPT) facility was constructed at the
Naval Surface Warfare Center (NSWC) Land-Based Engineering Site (LBES)
in Philadelphia, PA. NSWC was tasked to design, construct, and operate
the CWAS LBPT facility to support CWAS performance testing. NSWC in turn
tasked Fairmount Automation to design, develop, and integrate the
Control and Monitoring System (CMS) for the CWAS LBPT facility.
The need for the CMS was established by
the rigorous testing requirements of the CWAS. The requirements related
to the design (and usage) of the CWAS LBPT facility are described in BIW
Purchase Specification 503-532-12A, “Purchase Specification for Chilled
Water Automation System for DDG-51 Class Ships,” which states “CWAS
shall be tested…using a full-scale, reduced-scope demonstrator to verify
the damage detection, isolation, and reconfiguration capabilities [of
CWAS]. The test shall provide a means to simulate fluid system damage
across the full range of chilled water operating conditions, as well as
individually interrupt distributed control network communications
between CWAS node[s] and electrical power to each CWAS node.”
Fairmount Automation’s tasking included
the design of all CMS hardware configuration items (HWCIs), the design,
coding and testing of all CMS software configuration items (SCIs), and
the development of human computer interface (HCI) software. The CMS
provides the following capabilities to support the CWAS LBPT facility:
- Capability to remotely control,
and monitor the operation of the port chilled water loop (including
the chilled water plant that supplies the port loop).
- Capability to activate ruptures in
the port main loop and branch piping, interrupt (break) each DCN
segment between CWAS nodes, and interrupt electrical power to each
CWAS node.
- Capability to log test data (e.g.,
damage events imposed by the CMS, as well as pressures and
volumetric flow rates in key locations of the port chilled water
piping and plant).
Fairmount Automation was also
responsible for generating the CMS validation test plan and test
procedures and for submitting these documents to NSWC Code 923 for
review and approval. Fairmount Automation and NSWC Code 923 personnel
jointly conducted CMS validation testing. CMS testing verified:
- The CMS provides the capability to
independently control each rupture simulation valve from the Test
Operator Workstation (TOW) and verify the CMS data logging.
- The CMS provides the capability to
independently interrupt each DCN segment from the TOW and verify the
CMS data logging.
- The CMS provides the capability to
independently interrupt power to each CWAS component from the TOW
and verify CMS data logging.
- The CMS provides the capability to
control and monitor the chilled water plant including displaying
pump discharge and suction pressure, expansion tank level, array
supply pressures, and expansion tank level alarms, remotely starting
and stopping the pump, automatic shutdown of the pump on low level
condition, and emergency shutdown of the pump. Additionally, data
logging of all plant parameters with correct timestamps will be
verified.
- The CMS provides the capability to
control and monitor the chilled water branches including remote
control of valve position, automatic control of branch flow,
indication of branch flow rate, and indication of valve position
feedback. Additionally data logging of all branch flow parameters
with correct timestamps will be verified.
- The CMS executes damage scenarios
properly by verifying rupture valve relays, DCN interrupt relays,
and CWAS power interrupt relays activate at the times defined in the
damage scenario file. Additionally, ensure that the CMS
automatically logs data during the damage scenario and that damage
scenario execution may be halted via stop scenario command and/or
emergency shutdown command.
The CWAS LBPT facility design includes
a full-scale, port chilled water loop (5-inch diameter piping and
approximately 300 feet in length), and a simulated starboard chilled
water loop, architected by Fairmount Automation. The port loop contains
actual PAVs, while the starboard loop contains simulated PAV nodes
interfaced to a computer-based simulation of the starboard loop. The
CWAS vendor is providing the simulated PAV nodes and computer-based
simulation to implement the simulated starboard chilled water loop. The
CWAS LBPT facility also includes the complete CWAS distributed control
network (DCN) infrastructure (i.e., all CWAS nodes, gateways, routers,
and DCN segments).
Following successful CMS qualification
testing, Fairmount Automation turned over the CWAS LBPT to the CWAS test
team to support qualification testing in August 2005.
Click to return to the main Automated Damage Control Page.
|