Discrete Automation Module Type 1 with Isolated Outputs (DAM-1ISO)

Features and Benefits

  • Logic and Batch Control
  • Eight Isolated Form C Relays
  • Ten Auto-Detecting AC/DC Voltage Inputs
  • Integrated User Interface (Push Buttons and Displays)
  • Fully Sealed Enclosure (NEMA 4X, 6, 13 Protection)
  • -40°C to +65°C (-40°F to +149°F) Operating Range
  • MIL-STD-901D (Pending) Grade A for High Impact Shock
  • MIL-STD-167B (Pending) for Vibration
  • MIL-STD-461E (Pending) for Electro-Magnetic Interference (EMI)
  • Powerful and easy-to-use graphical programming
  • Supports Hot Swapping

The Chameleon Discrete Automation Module (DAM-1) offers high-performance logic and batch control. The DAM-1 module contains ten digital inputs, eight digital relay outputs, four user-programmable push-buttons, and eight user-addressable tri-color digital readouts that are configured in software. It is powered by an ARM processor with sufficient computational power to handle the most demanding applications. The DAM-1 embedded firmware is stored in its flash memory and is upgradeable: you can rest assured that the hardware investment you make in Chameleon will not become obsolete.

Its ten universal digital inputs are capable of accepting a broad range of AC and DC signals with no reconfiguration or rewiring required.  Its eight digital outputs are Form C mechanical relays.

The DAM-1 module is available in two wiring configurations for the digital outputs: isolated and banked. In the isolated wiring hub configuration, every relay output has a unique common, normally open, and normally closed terminal connection point. The banked wiring hub configuration provides two power termination groups and arranges the digital outputs into two banks of four relays—the relays in each bank have their common terminal tied together (but each relay maintains unique terminal points for the NO and NC contacts). While the isolated wiring hub configuration provides the most power sourcing flexibility, the banked wiring hub is advantageous in applications that have common power sources by eliminating the need to splice wires. When ordering, use DAM-1ISO for the isolated wiring hub configuration and DAM-1BK for the banked wiring hub configuration.

Each DAM-1 module provides convenient tag holders that can be associated with its digital readouts and push buttons. Multiple modules can be attached to each other to expand I/O capacity and to provide redundant I/O connections. They can also be combined with other Chameleon modules to form a full-featured programmable automation controller. As with all Chameleon modules, DAM-1 units are hot-swappable.

ENVIRONMENTAL CHARACTERISTICS
Operating Ambient Temperature Range-40°C to 65°C
Storage/Transport Ambient Temperature Range-40°C to 85°C
High Impact ShockMIL-STD-901D (Pending), Grade A
Mechanical VibrationMIL-STD-167B (Pending), 0-50Hz
Electro-Magnetic InterferenceMIL-STD-461E (Pending)
Facial/Housing ProtectionNEMA 1,2,4,4X,5,6,12,12K,13
  
DIGITAL INPUTS
Quantity10
Maximum Allowable Continuous Input Voltage80 VDC or 140 VAC RMS
Maximum Allowable Voltage Spike1000V peak 1.2µS x 50µS pulse per MIL-STD-1399 Section 300
Logic High Voltage Range5-80 VDC or 24-130 VAC RMS 55-500 Hz
Minimum Input Duration for Logic High Detection4 ms
Logic Low Voltage Range0-1 VDC or 0-0.5 VAC RMS 55-500 Hz
Minimum Input Duration For Logic Low Detection56 ms
Minimum Input Current Required (AC and DC inputs)

5mA RMS

Electrical Isolation: Digital Input to Digital Input, Control Circuitry or Chassis Ground

1240 VRMS for 1 minute

  
DIGITAL OUTPUTS
Quantity / Type8 Form “C” Relays
Close Time / Open Time5 ms typical (excluding bounce) / 7 ms typical (excluding bounce)
Voltage Rating140 VAC, 28VDC Resistive (Inductive Loads Require External Clamp)
Minimum Voltage to Guarantee Contact Conduction5V @ 100mA after break-in (silver nickel contacts)
Typical Contact Resistance20 mΩ @ 5A RMS
Minimum Contact Ratings
Load:Operations:Standard:
4.4A, 140VAC on the C/O contact
20/2A, 140VAC, PF=0.3 on the N/O contact
1.0 x 105
1.2 x 105
5 VDE 0435
AC 15
Maximum Allowed Continuous Current (Any Single Relay)4.4 Amps RMS
Maximum Allowed Combined Current (ALL Relays)16 Amps RMS with no single relay conducting more than 4.4 Amps
   NOTE:  If any single relay conducts more than 2A, refer to DAM-2 Power Spread Calculator for Allowable Configurations
Maximum Allowed Inrush Current (Any Single Relay)20 Amps RMS for 400 ms on make
Maximum Allowed Current During Hot Swap (Any Single Relay)4.4 Amps RMS
Inductive Load Minimum Power Factor (AC Only)40%
Electrical Isolation: Any Output to Control Circuitry or Chassis Ground Digital Output Bank A to Digital Output Bank B1240 VRMS (Bank to Bank) for 1 minute 350 VRMS (within a bank) for 1 minute
  
ELECTRICAL CHARACTERISTICS
Maximum Power Consumption1.3W + 0.03 W/mA x (current draw from aux. power source) + 0.05 W / relay x (number of relays in use)
Maximum Allowable Auxiliary Current250mA at 24VDC
Real-Time Clock Battery Life(Minimum; No power applied, 25°C)

10 Years

Supported Cable DiametersTwo glands 0.24”-0.47” and six glands 0.16”-0.31”
Supported Wire Gauges

16-28 AWG

  
OPERATOR INTERFACE
Digital ReadoutsEight user-programmable three-color (red/yellow/green) LEDs with label holders
Push-ButtonsFour user-programmable on/off buttons with label holders
Status ReadoutOne three-color (red/yellow/green) LED Indicator
IR Wireless Interface

115kbps SIR

  
PHYSICAL CHARACTERISTICS
Weight2.35 lbs
Front Panel Dimensions4” W x 6” L
Enclosure Height3″ H

The following part numbers can be used when ordering the DAM-1ISO.

Fairmount Part Number

Description

01012-326DAM-1ISO with Black Enclosure (without Stuffing Tubes)
01014-026DAM-1ISO Full Size Gray Enclosure and Wiring Hub
11047-202DAM-1 Active Board and Gray Cover
11047-252DAM-1 Active Board and Black Cover
01014-326DAM-1ISO Full Size Black Enclosure and Wiring Hub (without Stuffing Tubes)
11049-100DAM-1ISO/2ISO Wiring Hub Assembly